Asset Twin example

NDE - P100

Low Not assessed  Motor on Water treatment / WT-PMP-100

Not in alert.

Likely faults

FaultLikelihoodSeen on
VFD electrical noise 60% stream 0608afe4, stream 5053af13, stream c66ee645
Grease issue 50% stream 0608afe4
Flow turbulence 50% stream 0608afe4
Inner race bearing damage 50% stream 0608afe4, stream 5053af13
Soft foot 30% stream 0608afe4, stream 5053af13, stream c66ee645
Electrical interference 30% stream 0608afe4, stream 5053af13
Beating 20% stream 0608afe4, stream 5053af13
Loose connections 10% stream 0608afe4, stream 5053af13, stream c66ee645

Each axis is analysed on its own; a fault seen on several shows the highest likelihood any of them reports, never a sum.

What changed

Jump in Envelope Peak Score
Typical level of Envelope Peak Score has increased from <<1.94:g^2>> to <<4.9:g^2>>.
stream 5053af13 2026-10-16 11:23

Trends

Measurement time 2026-09-26 20:06 to 2026-10-27 13:40 (UTC). ▏went into alert · ▏back to low, cleared or as the evidence faded — from Multiviz's priority history.

Vibration level

How strongly the machine vibrates at this point. A rise here is what usually lies behind an alert: compare it with the alert marks.

Velocity RMS · mm/s Stream 0608afe4 2.11 mm/s Stream 5053af13 1.5 mm/s Stream c66ee645 1.83 mm/s
0 2 4 6 Oct 01 Oct 08 Oct 15 Oct 22

Reported by the sensor itself, about every 5 min. MultiViz also computes it from each waveform (about every 14 h); the sensor's value is shown because it comes more often. The two may differ: each uses its own frequency range.

Impacting

Short, sharp impacts, as from a damaged bearing, raise crest factor and kurtosis — often before the overall level moves.

Acceleration RMS · g Stream 0608afe4 0.355 g Stream 5053af13 0.351 g Stream c66ee645 0.381 g
0.0 0.5 1.0 1.5 Oct 08 Oct 22

Reported by the sensor itself, about every 5 min. MultiViz also computes it from each waveform (about every 14 h); the sensor's value is shown because it comes more often. The two may differ: each uses its own frequency range.

Crest factor · peak ÷ RMS, no unit Stream 0608afe4 3.41 Stream 5053af13 3.02 Stream c66ee645 3.13
2 3 4 5 Oct 08 Oct 22

Computed by MultiViz from each vibration measurement (waveform), about every 14 h.

Kurtosis · no unit; about 3 when nothing is impacting Stream 0608afe4 2.7 Stream 5053af13 2.71 Stream c66ee645 2.54
1.5 2.0 2.5 3.0 3.5 4.0 Oct 08 Oct 22

Computed by MultiViz from each vibration measurement (waveform), about every 14 h.

Operating conditions

What the machine was doing. A change in speed or temperature explains many changes in vibration.

Temperature · °C latest 24 °C
0 10 20 30 Oct 08 Oct 22

Reported by the sensor itself, about every 5 min.

Speed

Nothing recorded for this measuring point yet.

Sensor health

About the sensor, not the machine: a flat battery or a weak signal shows up as gaps in the data.

Sensor battery · % latest 100 %
90 95 100 105 110 Oct 08 Oct 22

Reported by the sensor itself, about every 5 min.

Signal strength · unit not reported latest -46
-50 -45 -40 -35 Oct 08 Oct 22

Reported by the sensor itself, about every 5 min.

Record a status

Your verdict, recorded here and sent to Multiviz as a clear of the point: its priority drops to low and rises again only on what is detected after now. It counts once Multiviz has accepted the clear.


Axes

AxisPriorityLatest measurement
Stream 0608afe4 Low 2026-10-26 20:04 Analysis and trends →
Stream 5053af13 Low 2026-10-26 20:04 Analysis and trends →
Stream c66ee645 Low 2026-10-26 20:04 Analysis and trends →

History

Priority

Each time the point's level changed, from Multiviz's priority history (bounded by the deployment). A fall to low says how the alert ended: a clear, or the evidence faded.

Data as ofPriorityWhat happenedBecause of
2026-10-26 20:04 Low — an analysis

Clears

Never cleared.