DE - 502
Medium Not assessed Fan on HVAC / HV-FAN-502
Medium In alert
09b36730, abcc6f92 at medium priority, data as of 2026-10-26 22:49. The evidence is below: the likely faults and what changed. The alert ends when the point is back at low: when someone acknowledges it, or by itself if newer measurements no longer support the change.
Likely faults
| Fault | Likelihood | Seen on |
|---|---|---|
| Rotating looseness | 70% | stream 09b36730, stream abcc6f92 |
| Lubrication issue | 60% | stream 4bf80077 |
| Process related loading | 40% | stream 4bf80077 |
| Process related harmonics | 30% | stream 09b36730, stream abcc6f92 |
Each axis is analysed on its own; a fault seen on several shows the highest likelihood any of them reports, never a sum.
What changed
| Low Frequency Change in velocity for low frequency band <<2-8:Hz>> for mode 5 has been detected. |
stream 09b36730, stream abcc6f92 | 2026-10-15 09:52 |
| Emerging Mode New mode 6 has been detected. |
stream abcc6f92 | 2026-10-15 09:52 |
| Jump in Envelope Peak Score Typical level of Envelope Peak Score has increased from <<1.36:g^2>> to <<2.72:g^2>>. |
stream 09b36730 | 2026-10-14 09:48 |
| RMS Increase An increase in RMS has been detected for mode 1 from <<0.719:g>> to <<1.408:g>>. |
stream 4bf80077 | 2026-10-14 09:48 |
| Emerging Mode New mode 5 has been detected. |
stream 09b36730 | 2026-10-11 10:14 |
| Jump in Envelope Peak Score Typical level of Envelope Peak Score has increased from <<0.92:g^2>> to <<2.59:g^2>>. |
stream abcc6f92 | 2026-10-11 10:14 |
| Low Frequency Change in velocity for low frequency band <<17-23:Hz>> for mode 2 has been detected. |
stream 09b36730 | 2026-10-04 02:03 |
| RMS Increase An increase in RMS has been detected for mode 2 from <<0.457:g>> to <<0.683:g>>. |
stream 09b36730 | 2026-10-04 02:03 |
| Low Frequency Change in velocity for low frequency band <<2-8:Hz>> for mode 1 has been detected. |
stream 4bf80077 | 2026-10-04 02:03 |
| Low Frequency Change in velocity for low frequency band <<12-18:Hz>> for mode 1 has been detected. |
stream 09b36730 | 2026-09-28 17:25 |
Trends
Measurement time 2026-09-26 22:54 to 2026-10-27 13:38 (UTC). ▏went into alert · ▏back to low, cleared or as the evidence faded — from Multiviz's priority history.
Vibration level
How strongly the machine vibrates at this point. A rise here is what usually lies behind an alert: compare it with the alert marks.
Reported by the sensor itself, about every 5 min. MultiViz also computes it from each waveform (about every 13 h); the sensor's value is shown because it comes more often. The two may differ: each uses its own frequency range.
Impacting
Short, sharp impacts, as from a damaged bearing, raise crest factor and kurtosis — often before the overall level moves.
Reported by the sensor itself, about every 5 min. MultiViz also computes it from each waveform (about every 13 h); the sensor's value is shown because it comes more often. The two may differ: each uses its own frequency range.
Computed by MultiViz from each vibration measurement (waveform), about every 13 h.
Computed by MultiViz from each vibration measurement (waveform), about every 13 h.
Operating conditions
What the machine was doing. A change in speed or temperature explains many changes in vibration.
Reported by the sensor itself, about every 5 min.
Nothing recorded for this measuring point yet.
Sensor health
About the sensor, not the machine: a flat battery or a weak signal shows up as gaps in the data.
Reported by the sensor itself, about every 5 min.
Reported by the sensor itself, about every 5 min.
Acknowledge
Your verdict, recorded here and sent to Multiviz as a clear of the point: its priority drops to low and rises again only on what is detected after now. That ends the alert. It counts once Multiviz has accepted the clear.
Axes
| Axis | Priority | Latest measurement | |
|---|---|---|---|
| Stream 09b36730 — sets the priority | Medium | 2026-10-26 22:49 | Analysis and trends → |
| Stream 4bf80077 | Low | 2026-10-26 22:49 | Analysis and trends → |
| Stream abcc6f92 | Medium | 2026-10-26 22:49 | Analysis and trends → |
History
Priority
Each time the point's level changed, from Multiviz's priority history (bounded by the deployment). A fall to low says how the alert ended: a clear, or the evidence faded.
| Data as of | Priority | What happened | Because of |
|---|---|---|---|
| 2026-10-26 22:49 | Medium | Went into alert | an analysis |
| 2026-10-26 22:49 | Low | — | an analysis |
Clears
Never cleared.