Asset Twin example

DE - P100

Low Not assessed  Motor on Water treatment / WT-PMP-100

Not in alert.

Likely faults

FaultLikelihoodSeen on
Rotating looseness 70% stream 7ae29355
VFD electrical noise 60% stream 1a891f03, stream 7ae29355, stream d9fd8d17
Soft foot 30% stream 1a891f03, stream 7ae29355, stream d9fd8d17
Process related harmonics 30% stream 7ae29355
Loose connections 10% stream 1a891f03, stream 7ae29355, stream d9fd8d17

Each axis is analysed on its own; a fault seen on several shows the highest likelihood any of them reports, never a sum.

What changed

No active changes.

Trends

Measurement time 2026-09-26 12:25 to 2026-10-27 13:38 (UTC). ▏went into alert · ▏back to low, cleared or as the evidence faded — from Multiviz's priority history.

Vibration level

How strongly the machine vibrates at this point. A rise here is what usually lies behind an alert: compare it with the alert marks.

Velocity RMS · mm/s Stream 1a891f03 1.75 mm/s Stream 7ae29355 2.79 mm/s Stream d9fd8d17 4.93 mm/s
0.0 2.5 5.0 7.5 10.0 Oct 01 Oct 08 Oct 15 Oct 22

Reported by the sensor itself, about every 5 min. MultiViz also computes it from each waveform (about every 13.5 h); the sensor's value is shown because it comes more often. The two may differ: each uses its own frequency range.

Impacting

Short, sharp impacts, as from a damaged bearing, raise crest factor and kurtosis — often before the overall level moves.

Acceleration RMS · g Stream 1a891f03 0.626 g Stream 7ae29355 0.476 g Stream d9fd8d17 2.76 g
0 1 2 3 4 Oct 08 Oct 22

Reported by the sensor itself, about every 5 min. MultiViz also computes it from each waveform (about every 13.5 h); the sensor's value is shown because it comes more often. The two may differ: each uses its own frequency range.

Crest factor · peak ÷ RMS, no unit Stream 1a891f03 3.08 Stream 7ae29355 3.16 Stream d9fd8d17 3.39
0 2 4 6 Oct 08 Oct 22

Computed by MultiViz from each vibration measurement (waveform), about every 13.5 h.

Kurtosis · no unit; about 3 when nothing is impacting Stream 1a891f03 2.64 Stream 7ae29355 2.64 Stream d9fd8d17 2.76
0 1 2 3 4 Oct 08 Oct 22

Computed by MultiViz from each vibration measurement (waveform), about every 13.5 h.

Operating conditions

What the machine was doing. A change in speed or temperature explains many changes in vibration.

Temperature · °C latest 24 °C
0 10 20 30 Oct 08 Oct 22

Reported by the sensor itself, about every 5 min.

Speed

Nothing recorded for this measuring point yet.

Sensor health

About the sensor, not the machine: a flat battery or a weak signal shows up as gaps in the data.

Sensor battery · % latest 100 %
90 95 100 105 110 Oct 08 Oct 22

Reported by the sensor itself, about every 5 min.

Signal strength · unit not reported latest -40
-70 -60 -50 -40 -30 Oct 08 Oct 22

Reported by the sensor itself, about every 5 min.

Record a status

Your verdict, recorded here and sent to Multiviz as a clear of the point: its priority drops to low and rises again only on what is detected after now. It counts once Multiviz has accepted the clear.


Axes

AxisPriorityLatest measurement
Stream 1a891f03 Low 2026-10-26 12:22 Analysis and trends →
Stream 7ae29355 Low 2026-10-26 12:22 Analysis and trends →
Stream d9fd8d17 Low 2026-10-26 12:22 Analysis and trends →

History

Priority

Each time the point's level changed, from Multiviz's priority history (bounded by the deployment). A fall to low says how the alert ended: a clear, or the evidence faded.

Data as ofPriorityWhat happenedBecause of
2026-10-26 12:22 Low — an analysis

Clears

Never cleared.